Soffits a soffit encloses the underside of sloped or flat roof overhangs.
1 hour roof over hang protection.
See attached image we are hoping to replicate this in the addition.
Wall framing whichever is closer to one of the following.
The irc in table r302 1 1 only.
Ibc section 703 3 item 2.
The existing open eaves have t g sheathing with exposed rafter tails and 2x blocking b w rafters.
To the closest interior lot line.
Prescriptive designs ibc table 721 3 item 21 1 1 describes a single prescriptive 1 hour rated floor or roof assembly that includes wood trusses.
Overhangs such as roof eaves and soffits are one element needing protection.
The ibc provides options while the irc has only one method of compliance.
To an imaginary line between two buildings on the lot.
Use flat horizontal soffits see figure 3 instead of attaching the soffits to the sloped joists which creates sloped soffits.
For complete information on the listed systems the actual listing or test report should be reviewed.
Madesign history contact.
Roof overhangs must have a one hour fire protection on the underside when less than 5 from the property line and cannot project closer than 2 from the line.
However a garage located within 2 of the property line is permitted to have a 4 inch roof eave projection.
The ibc in section 705 2 3 permits the use of type iv construction fire retardant treated wood or 1 hr fire resistance construction for combustible projections.
1 hour rated wall and protected eave overhang soffit board 1 2 cdx ply 2 x 4 block 2x framing 5 8 type x gypsum sheathing siding 5 8 type x gypsum wallboard structural sheathing as required fascia approved roof covering alternate location of gwb or 2x blocking if no ceiling finish is provided 1900 sw 4th avenue suite 5000 portland or 97201.
Overhangs can be open in which the trusses rafters and decking are exposed see figure 1 or enclosed by a soffit.
Roof ceiling and attic separation.
Hi all we need to provide one hour rated protection for under eaves on a residential property remodel.
Eave overhang fire protection.
Walls less than 5 feet from the property lot line must be of a listed hour fire1 resistant construction.